The DS 40SE has passed extensive testing and complies with the following specifications and uses:
LISTED to ANSI/UL 1480-2005
Fire Protective Signaling Use – UL Ca
tegory UUMW, File Number S 3241.
Control Number 42S9 when installed with a junction box (on-wall or in-wall).
Not for use with DC-supervised systems.
General-Purpose Use – UL Category UEAY, Fi
le Number S 5591 Control Number 3N89.
Suitable for use outdoors in wet locations.
Suitable for installation using
Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2008,
Article 640.
Suitable for use with fire alarm circuit wir
ing methods in accordance with NFPA 70, National Electric Code, 2008, Article 760.
The DS 40SE has been designed to the requir
ements defined in the following European regulatory specification for combination systems:
British Standard Code of Practice BS 5839, Part 8.
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage ANSI/UL 1480-2005
Tap 70V 100V
2.5 Watt 81 dBA
5 Watt 84 dBA 84 dBA
10 Watt 87 dBA 86 dBA
20 Watt 89 dBA 89 dBA
40 Watt 92 dBA 92 dBA
8 Ohm 91 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm: 400 Hz to 4 kHz
General signaling: 80 Hz to 16 kHz (±3dB)
Wire gauge
The FreeSpace
®
DS 40SE loudspeaker bracket is designed to work with 18 AWG (0.8 mm
2
) to 14 AWG (2.0 mm
2
) size wire only.