Bose ControlSpace CC-16 Installation Guide Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 17
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Page 18 User Guide English
Installation and Operating Guide pro.Bose.com
7. Connect GPIO devices
General Purpose Inputs
General-purpose control input ports are used to connect external hardware such as potentiometers (to control levels or gains) and
switches (to invoke parameter sets). Using ControlSpace
®
Designer
software, functions can easily be assigned to these external
controls. In addition, Bose offers three GPI-compatible interfaces, the CC-4 room controller, the Volume Control with A/B switch user
interface, and the Volume Control user interface.
General Purpose Outputs
General Purpose Inputs/Outpus (GPIO)
Five control inputs (GPI) and five controls outputs (GPO) are
available and can be used to interface the ESP processor
with external control hardware.
10k potentiometer
Using Switches
Both toggle switches and pushbuttons can be used
with control inputs. Each input terminal is tied to an
internal pull-up resistor (2k ohm) so that external
switches can be wired directly from input to ground.
Using Potentiometers
10k ohm potentiometers can be connected and
associated with control gain blocks in a system design.
Inputs are compatible (through ControlSpace Designer
software) with linear taper potentiometers wired for
minimum resistance at the full-clockwise position or at
the full-counterclockwise position.
Current Source Devices
Some devices such as LEDs and low-current relays can be
powered directly from control outputs. A maximum source
current of 10 mA is available.
Source Limits: 8 VDC, 10 mA (max.).
Current Sink Devices
Devices that require more current than is available from a current-
source configuration can use control outputs to sink up to 100mA
when used with external power supplies. Use proper precautions
when driving inductive loads.
Sink Limits: 100 mA (max.). External supplies must be 24 VDC.
Toggle
switch
Push
button
LED
Anode Cathode
Current
Limiting
Resistor
External
Supply
(24 VDC Max.)
Relay
(Rated Current of Coil <100 mA
Page view 10